EN
Home Products ExMax / RedMax / InMax
ATEX certified IECEx Zone 1 · 2 · 21 · 22

ExMax / RedMax / InMax.

Quarter-turn rotary actuator in three versions: ExMax for Zones 1, 2, 21, 22, RedMax for the less demanding Zones 2 and 22, InMax for standard non-hazardous areas. Certified to ATEX, IECEx, UL, CSA and INMETRO.

5–150 NmS: 5–30 Nm · M: 24–150 Nm
95°angle of rotation (+ 5° preload)
IP66 / IP67protection rating (S / M)
24–240 VAC/DC universal power supply
–40 °Cmin. temperature (int. heater; F1/F3: –20 °C)
ExMax-S – rotary actuator for potentially explosive atmospheres ATEX certification

Key features

  • Quarter-turn actuator, 95° angle of rotation (incl. ~5° preload), direct mounting on the damper shaft
  • Universal power supply 24–240 V AC/DC, self-adapting without switching (CY version: 24 V)
  • 5 running times adjustable directly on site, no special tools required
  • Fail-safe spring return to the safe position on power failure (variants F/BF/F1/F3)
  • Integrated Ex-i circuit for direct connection of the ExPro-TT thermal trip (BF variants)
  • 2 integrated auxiliary switches for position feedback (5° and 85°) – variants -S, -SF, -SF1, -SF3 and -BF…
  • Integrated controlled heater – operation down to –40 °C (variants F1/F3 from –20 °C)
  • 100% overload protection, self-locking on the S series
  • Modulating control with position feedback: -Y 0–10 V / 4–20 mA, -CY 4–20 mA input (0–10 V feedback)

Applications

HVAC dampers Fire dampers Ball valves Butterfly valves Noise attenuation Flow control

Technical data

Mechanical

Angle of rotation
95° (incl. ~5° preload)
Output shaft – S
Double square 12 × 12 mm (direct coupling)
Output shaft – M
Double square 16 × 16 mm (direct coupling)
Dimensions – S series
210 × 95 × 80 mm (L × W × H)
Dimensions – M series
~288 × 149 × 116 mm (L × W × H)
Weight – S series
~3.5 kg
Weight – M series
~9.5 kg
Motor
Brushless DC motor
Housing
Aluminium / -CTS (S series) or -CTM (M series) marine coating / -VAS/-VAM stainless steel
Controls
10-position switch, push button, 3-colour LED (calibration)
Emergency operation
Manual, with the supplied key (max. 4 Nm)

Torque and speed

Torque – S series
5 / 10 / 15 / 30 Nm (adjustable on site)
Torque – M series
24 / 30 / 40 / 50 / 60 / 75 / 100 / 150 Nm (24 and 40 Nm = spring torque for -F3)
Running times – S series
On/off, 3-pos. (3P/F/BF/F1): 3/15/30/60/120 s/90° · Modulating (Y/CY): 7.5/15/30/60/120 s/90° · Multi-turn (R): 60/120/240/480 s/360°
Running times – M series
40 / 60 / 90 / 120 / 150 s/90° (types 150 and 60-…F: 40–120 s/90° only)
Fail-safe run – S series
~1 s (F1) · ~3 or ~10 s (BF/F) after power failure
Fail-safe run – M series
~3 s (F3) · ~20 s (BF/YF) after power failure

Electrical

Power supply
24–240 V AC/DC ±10% (CY: 24 V only)
Frequency
50–60 Hz ±20%
Power consumption
~4–11 W on/off (depending on voltage) · ~7–17 W F1/F3 · ~8–20 W modulating Y (CY: ~8–12 W) · ~16 W heater
Cable gland
M16 × 1.5 mm · cable ~1 m, 0.5 mm²

Environment and certification

Protection rating
IP66 (S series) / IP67 (M series)
Operating temperature
–40…+40 °C (T6) / –40…+50 °C (T5); F1/F3: from –20 °C · storage –40…+70 °C
Humidity
0–90% rH, non-condensing
ATEX category
II 2(2)G / II 2(2)D
ATEX marking
Ex db [ib Gb] IIC T6, T5 Gb / Ex tb [ib Db] IIIC T80 °C, T95 °C Db

Select the required actuator features – the configurator immediately shows the matching model with a link to its datasheet, including the correct series for the installation zone.

Depending on the selected zone, the configurator switches both the recommended model and the datasheet link: ExMax (Zones 1, 2, 21, 22), RedMax (Zones 2, 22 – more cost-effective), InMax (non-hazardous areas). If no RedMax exists for the given variant, ExMax is shown – it is also suitable for Zone 2/22.

Model designation key

What the suffixes and codes in the ExMax designation mean

S / M

Size series according to the required torque: S = 5–30 Nm, M = 24–150 Nm. Physically and dimensionally, these are two different design series.

5.10 · 15.30 · 50.75 …

The number in the designation = available torque values in Nm, adjustable directly on the actuator without tools (e.g. “5.10” = 5 or 10 Nm). For variants -F1/-SF1/-BF1 and -F3/-SF3/-BF3, the number indicates the motor torque; the spring torque is lower (ExMax-8-F1: ~6 Nm, ExMax-15-F1: ~12 Nm, ExMax-30-F3: ~24 Nm, ExMax-50-F3: ~40 Nm).

-F · -SF · -YF · -CYF · -BF · -F1 · -SF1 · -BF1 · -F3 · -SF3 · -BF3

Fail-safe spring return to the safe position on power failure. Speed depending on type: ~1 s (F1/SF1/BF1) · ~3 s (F3/SF3/BF3) · S series (F/SF/YF/BF): ~3 or ~10 s, selectable · -CYF: ~10 s · M series (F/SF/YF/BF): ~20 s.

-S · -SF

2 integrated auxiliary switches for position feedback (switching at 5° and 85°).

-Y · -YF

Modulating control (0–10 V or 4–20 mA) with position feedback.

-CY · -CYF

4–20 mA input (24 V only), intended for use with the ExReg/InReg controller (VAV control). -CYF additionally with fail-safe spring (~10 s).

-BF · -BF1 · -BF3

Integrated Ex-i circuit for direct connection of the ExPro-TT thermal trip (typically fire dampers).

-R

Multi-turn operation (n × 360°) – for valves and fittings requiring rotation beyond 90°.

-CTS / -CTM

Optional aluminium housing with seawater-resistant coating (S / M series).

-VAS / -VAM

Optional all-stainless-steel housing for aggressive environments – chemical, pharmaceutical (S / M series).

Add-ons and accessories that can be combined with ExMax / RedMax / InMax actuators.

ExLin

ExLin

Conversion kit – turns an actuator in the -F variant into a linear stroke drive for globe valves. 6 strokes 7.5–42 mm.

ExPro-TT

ExPro-TT / InPro-TT

Thermal trip for fire dampers, exclusively for ExMax/RedMax-BF actuators. InPro-TT for standard (non-hazardous) areas.

ExPolar

ExPolar / InPolar · ExArctic / InArctic

Controlled heating system with protective jacket for actuator operation at temperatures down to –50 °C (ExPolar) or down to –60 °C (ExArctic, for both Max and Run actuators, on request).

ExSwitch

ExSwitch / RedSwitch / InSwitch

Add-on switch module – 2 volt-free contacts, adjustable on site, retrofittable on size S and M actuators.

ExBox

ExBox / RedBox / InBox

Ex-e terminal/junction box for retrofitting on Max actuators and Run linear actuators.

MKK-S

MKK-S

Mounting bracket for ..Box terminal boxes (the two dots stand for the prefix Ex/Red/In) – direct mounting on size S actuators.

MKK-M

MKK-M

Mounting bracket for ..Box terminal boxes – direct mounting on size M actuators.

KB-S

KB-S

Damper shaft clamp – round Ø 10–20 mm or square 10–16 mm, incl. bracket, size S.

AR-12-xx

AR-12-xx

Square shaft reducer from 12 × 12 mm to 11/10/9/8 mm, size S (e.g. AR-12-08).

AR-16-xx

AR-16-xx

Square shaft reducer from 16 × 16 mm to 14/12 mm, size M (e.g. AR-16-12).

Mechanical actuator accessories

Mounting, manual override and adaptation to the damper shaft – according to the Schischek product catalogue

Small mechanical parts without a separate datasheet – the specification is part of the product catalogue (see the Downloads tab). No manufacturer photo available.

CodeFunction
KB-AShaft coupling Ø ½" for North American dampers, size S
HV-SKU / HV-SLUManual override for size S – short / long version (for use with ..Box/..Switch)
HV-MUManual override for size M
DWB-S / DWB-MAngle of rotation limiter for size S / M
Retrofit-Kit-S / -MMechanical adaptation for replacing an older EXT series actuator (size S / M)
ADS / ADMAdaptation to specific valve and fitting types, size S / M – on request
WS-S / WS-MStainless steel weather protection cover for size S / M

ATEX – Ex db [ib Gb] IIC T6, T5 Gb

EPS17ATEX1132X

European certification for explosive gas atmospheres. Category 2G – intended for Zones 1 and 2 with explosive gases and vapours of group IIC (hydrogen, acetylene).

Zone 1 Zone 2

ATEX – Ex tb IIIC T80 °C Db

EPS17ATEX1132X

Certification for explosive dust atmospheres. Category 2D – Zones 21 and 22 with explosive dusts of group IIIC (metal dust, conductive dusts).

Zone 21 Zone 22

IECEx

IECEx EPS 17.0065X

International IECEx certification for use outside the EU – e.g. Australia, the Middle East, South America. Covers both gas and dust zones.

Zone 1 Zone 2 Zone 21 Zone 22

CE – Declaration of Conformity

EU Declaration of Conformity

Declaration of conformity with the directives ATEX 2014/34/EU, EMC 2014/30/EU, LVD 2014/35/EU and RoHS 2011/65/EU. Available for download as a PDF document.

UL / CSA

UL E340805 · CSA 2236405

UL: certificate E340805 to UL 61010-1 (electrical safety). CSA (C/US): certificate 2236405 for Class I, Division 1, Groups B, C, D; Class II, Division 1; Zone 1 AEx db [ib] IIC – valid for both the USA and Canada.

INMETRO (Brazil)

IEx 18.0034X (ExMax) · IEx 18.0224X (RedMax)

Certification for the Brazilian market to ABNT NBR IEC 60079, issued by the accredited body IEx Certificações. Allows direct use in Brazilian industry without local re-certification.

Catalogue

Datasheets – S series (individual variants)

Datasheets – M series (individual variants)

Installation manuals

Certificates

Declarations of conformity