EN
Home Products ExLin
IECEx certification Zone 1 · 2 · 21 · 22

ExLin.

A mechanical conversion kit that adds a linear stroke to an ExMax/RedMax/InMax-F rotary actuator for direct operation of valves. The kit has its own IECEx certificate; power supply and control are provided by the base actuator.

7.5–42 mmmax. stroke (6 models)
500–3,000 Nnominal force (up to 6,000 N at 0…+40 °C)
IP66degree of protection
~4.3 kgkit weight
–20…+50 °Coperating temperature
ExMax + LIN-20 on a 3-way valve ATEX certification

Key features

  • Mechanical kit – no electronics, motor or control of its own
  • Mounts on an ExMax/RedMax/InMax rotary actuator, size S or M, exclusively the -F variant (spring return)
  • 6 models by max. stroke: 7.5 / 10 / 15 / 20 / 30 / 42 mm
  • Anodised aluminium housing (AlMg4.5), stroke rod and adapter in V4A/AISI 316L stainless steel
  • Optional -CT variant with C5-M coating for marine environments
  • The valve adaptation is ordered to suit the valve manufacturer, type and nominal size DN

Applications

Globe (plug) valves 3-way valves HVAC control
ExLin is an add-on to the ExMax/RedMax/InMax actuator – power supply, control and feedback are all provided by the base actuator. Only the -F variants (spring return) are compatible, not the fast variants with a return time of 1 s (S) or 3 s (M).

Technical data

Mechanics

Kit dimensions
160 × 141 × 206 mm
Weight
~4.3 kg
Housing material
Anodised aluminium (AlMg4.5)
Stroke rod / adapter
Stainless steel V4A / AISI 316L
Degree of protection
IP66

Force and compatibility

Nominal force (–20…+40 °C)
500–3,000 N
Nominal force (0…+40 °C)
Up to 6,000 N
Blocking force
3–4× higher than nominal – size the valve with a margin
Compatible actuators
ExMax/RedMax/InMax, sizes S and M, -F variants only
Not compatible
Fast spring return variants (1 s for S, 3 s for M)

Environment and certification

Operating temperature
–20…+50 °C
Type of protection
Ex h (constructional safety, no electrics)
Marking (IECEx)
Ex h IIC T6/T5/T4 Gb / Ex h IIIC T80/T95/T130 °C Db

ExLin is available in 6 models by maximum stroke. If the required stroke lies between two values, the manufacturer specifies that the next larger model is always used.

ModelMax. stroke
LIN-7.57.5 mm
LIN-1010 mm
LIN-1515 mm
LIN-2020 mm
LIN-3030 mm
LIN-4042 mm

Designation overview

What the designation and optional suffixes mean

LIN-xx

Number = maximum stroke in mm (except LIN-40, which has 42 mm).

-F

The base actuator must be a spring return version – the kit does not work without -F.

-CT

Optional C5-M marine coating + stainless steel fittings for offshore applications.

IECEx – Ex h IIC T6/T5/T4 Gb

IECEx EPS 20.0029X

Separate certificate for the mechanical kit (no electrical circuits) – type of protection “Ex h” = constructional safety. Dust part: Ex h IIIC T80/T95/T130 °C Db.

Assembly certification

LIN + base actuator

The installed assembly is covered by both the ExLin kit certificate and the separate electrical ATEX/IECEx certificate of the ExMax/RedMax base actuator.

Datasheet

Certificate