EN
Home Products ExReg / InReg
ATEX certified IECEx Zone 1 · 2 · 21 · 22

ExReg / InReg.

Electronic volume flow and pressure controller (VAV/CAV) in two versions: ExReg for Zones 1, 2, 21, 22, InReg for standard non-hazardous areas. It directly controls a connected ExMax-…-CY actuator (InReg: InMax-…-CY) without the need for an additional Ex-i module in the control cabinet.

0–100…1,000 Papressure range (3 models)
4 modesflow or pressure controller/sensor
IP66protection rating
24 VAC/DC power supply +15%
–20…+50 °Coperating temperature
ExReg-V – volume flow and pressure controller for potentially explosive atmospheres ATEX certification

Key features

  • Piezo pressure sensor and controller in one compact housing – no external module or intrinsically safe wiring in the control cabinet
  • 4 switchable modes: flow controller (VAV/CAV), flow sensor, pressure controller, pressure sensor
  • Adaptive PID control, adjustable directly on site via a backlit display and 3 buttons
  • Controls only the ExMax actuator (InReg: InMax) in the -CY / -CYF variant
  • 24 V AC/DC power supply, 4–20 mA and 0–10 V outputs (setpoint, actual value, actuator position)
  • IP66 aluminium housing, optionally in all-stainless-steel or offshore version
  • Also available as InReg for standard non-hazardous areas

Applications

VAV/CAV flow control Duct pressure control BMS integration HVAC in Ex zones
ExReg is installed exclusively with the ExMax actuator (InReg with the InMax actuator) in the -CY / -CYF variant (4–20 mA input, 24 V only) – it does not support any other actuator. The combination forms a complete control loop without the need for an additional control system.

Technical data

Mechanical

Dimensions – aluminium
~180 × 107 × 66 mm
Dimensions – stainless steel
~195 × 127 × 70 mm
Weight – aluminium
~950 g
Weight – stainless steel
~2.5 kg
Cable glands
2× M16×1.5 (standard) · M20×1.5 (-VA/-OCT/-OVA)

Measurement and signal

Range
0–100 / 0–300 / 0–1,000 Pa (depending on model)
Sensor
Piezo pressure sensor, accuracy ±2.5% of range ±1 Pa
Min. measuring range
2% of full range
Outputs
4–20 mA (invertible), 0–10 V (setpoint/actual value/position)
Alarm contact
Relay 30 V / 0.1 A
Control
Auto / PID adaptive / PID normal

Electrical

Power supply
24 V AC/DC +15%, 50/60 Hz
Power consumption
150 mA / max. 3 W
Galvanic isolation
min. 1.5 kV

Environment and certification

Protection rating
IP66 to EN 60529
Operating temperature
–20…+50 °C (storage –35…+70 °C)
Humidity
0–95% rH, non-condensing
ATEX marking – gas
II 2(1) G Ex eb mb ib [ia Ga] IIC T6 Gb
ATEX marking – dust
II 2(1) D Ex tb ib [ia Da] IIIC T80 °C Db

ExReg-V is manufactured in three measuring ranges, each available in 5 housing versions depending on the installation environment. The same model also exists as InReg-V for standard non-hazardous areas.

ExReg-V Measuring ranges

The model defines the full pressure range in Pa

Model Pressure range Modes Actuator
ExReg-V-100-A0–100 PaVAV/CAV · pressureExMax-…-CY (InReg: InMax-…-CY)
ExReg-V-300-A0–300 PaVAV/CAV · pressureExMax-…-CY (InReg: InMax-…-CY)
ExReg-V-1000-A0–1,000 PaVAV/CAV · pressureExMax-…-CY (InReg: InMax-…-CY)

Designation key

What the suffixes and zone variants mean

100 · 300 · 1000

Number in the designation = full pressure measuring range in Pa.

-A

Standard aluminium housing.

-CT

Aluminium housing with seawater-resistant coating.

-OCT

Offshore version – aluminium + seawater-resistant coating, stainless steel connection tubes.

-VA

All-stainless-steel housing for chemically aggressive environments.

-OVA

Offshore version in all-stainless-steel design.

InReg

Version for standard areas (NOT intended for potentially explosive atmospheres) – same parameters and dimensions.

-…-CY

The only variant of the ExMax actuator (for ExReg) and InMax (for InReg) compatible with the controller.

For complete VAV/CAV control, ExReg-V requires the ExMax-…-CY/-CYF actuator (InReg-V: InMax-…-CY/-CYF) and installation accessories for connecting the pressure tubes to the damper.

Mounting and installation accessories

Details and datasheets – see the Accessories page

Small mounting accessories without a separate datasheet of their own. A complete overview including available datasheets can be found on the central Accessories page.

CodeFunction
Installation-Kit-2Installation kit for ExReg-V – 2 m pressure tube (Ø 6 mm) + 2 plastic nipples
MKR-VA/ALMounting bracket for installation on round ducts up to Ø 600 mm
WS-CBRStainless steel weather protection cover for outdoor installations

Details and datasheets: Accessories

ATEX – Ex eb mb ib [ia Ga] IIC T6 Gb

EPS11ATEX1380X

European certification for explosive gas atmospheres. Category 2(1)G – Zones 1 and 2, group IIC.

Zone 1 Zone 2

ATEX – Ex tb ib [ia Da] IIIC T80 °C Db

EPS11ATEX1380X

Certification for dust atmospheres, category 2(1)D.

Zone 21 Zone 22

IECEx

IECEx EPS 12.0028X

International IECEx certification for use outside the EU. Covers both gas and dust zones.

InReg – without Ex certification

EU DoC only

The version for standard areas has no ATEX or IECEx certificate – only a declaration of conformity.

Catalogue and datasheets

Accessories

Certificates

Declarations of conformity