EN
Home Products ExSens
Ex-i intrinsic safety Zone 1 · 2 · 22

ExSens.

Passive temperature, humidity and pressure sensor probes for mounting directly in the hazardous area. No electronics of their own – the signal is evaluated via an ExLine module (in a control cabinet in the safe area) or an ExBin-A switching module (mounted directly in the Ex zone).

23 typestemperature, humidity, pressure, flow
Pt100/Pt1000resistance sensor (analogue types)
–50…+250 °Crange depending on probe version
IP20–IP68protection rating depending on mounting type
Passiveno electronics of their own
ExSens TFK-2G3D – duct temperature probe ATEX certification

Key features

  • Fully passive probe – no electronics, no power supply of its own in the Ex zone
  • Analogue types (resistance Pt100/Pt1000, %rH) and switching types (potential-free contact)
  • Versions for rooms, ducts (flange-mounted) and liquids/gases (immersion)
  • Stainless steel probe sheaths (1.4571), PTFE or silicone cables for extreme temperatures
  • Intrinsic safety to EN 60079-11 (classified as “simple apparatus”)

Applications

Air/duct temperature Relative humidity Differential pressure Temperature of liquids and gases Air and liquid flow
The probe signal is evaluated via an ExLine module in the safe area (analogue and switching types) or via an ExBin-A mounted directly in the Ex zone (switching types) – the probe itself has no Ex marking of its own, as it is “simple apparatus”.

Technical data

Analogue temperature probes (Pt100/Pt1000)

TFFR-2G (room)
Temperature ±0.5 °C + 0–100% rH, 0…+50 °C, IP20
TFR-2G (room)
Pt100/Pt1000, –30…+60 °C, IP30
TFR-2G3D (room)
Pt100/Pt1000, –30…+60 °C, IP65, also Zone 22
TFK-2G3D (duct)
Probe 100/200/300/400 mm, measuring range –30…+150 °C (head ambient temperature –30…+60 °C), IP65
TFH-2G (cable)
Stainless steel sheath Ø9 mm, –50…+250 °C depending on cable, IP68 (-IP68 version)
TFM-2G (averaging, duct)
Pt100, capillary 0.4/3/6 m, –20…+70 °C, IP65
TFR-AN-2G3D (contact)
Pt100 with clamping strap, –30…+110 °C, IP65, Zone 22

Analogue humidity probes

FFR-2G (room)
0–100% rH, 0…+50 °C, IP20
FFK-2G (duct)
0–100% rH, 0…+60 °C, housing IP64 (probe IP40)

Thermostats (switching contact)

TBT-2G (immersion)
0–60/0–90/0–120/50–140 °C, IP65/IP54 (VA)
TBT-...-U-2G (immersion, internal)
0–90/0–120 °C (VA also –35…+35 °C), IP65/IP54/IP20 (FF)
TBK-FR-2G (frost protection)
–10…+15 °C, capillary 1.8/3/6 m, IP65
TBK-2G (duct)
0–60/0–90/50–140 °C, capillary, IP20
TBR-2G (room)
0–40/0–60 °C, IP54
TBR-2G3D (room)
–35…+30/0…+60 °C, IP65, also Zone 22
TBR-2-2G (room, two-stage)
0–40 °C, 2 independent microswitches, IP54

Pressure, flow and humidity switches

DBK-2G (pressure)
5 ranges 20–5,000 Pa, IP54, –20…+50 °C
DBK-2G3D (pressure)
4 ranges 40–5,000 Pa, IP65, –30…+60 °C
LGW-2G-…-SIL (pressure, SIL)
4 ranges 40–15,000 Pa, IP54
WFBK-2G (air flow)
Vane relay, switches from approx. 1 m/s, IP65
SWBT-2G (liquid flow)
Max. 11 bar, brass/stainless steel, IP65
FBR-2G (humidity, room)
35–100% rH, IP20
FBK-2G (humidity, duct)
35–95% rH, IP44

Environment and certification

Classification
Simple apparatus (EN 60079-11, cl. 5.7)
Zones 1, 2, 22 (incl. dust)
TFK-2G3D, TFR-2G3D, TFR-AN-2G3D, TBR-2G3D, DBK-2G3D
Zones 1, 2 (gases only)
All other probe types

Intrinsic safety (Ex-i parameters)

Analogue probes (TF.../FF...)
Max. probe input values: Ui=30 V, Ii=50 mA, Pi=100 mW (recommended transmitter EXL-IM-9182: Uo=6.5 V, Io=19.7 mA, Po=32 mW)
Switching probes (TB.../FB.../DBK/LGW/WFBK/SWBT)
Max. probe input values: Ui=30 V, Ii=50 mA, Pi=100 mW (recommended transmitter EXL-IR-9170: Uo=9.6 V, Io=10 mA, Po=24 mW)

ExSens comprises 23 probe types according to the measured variable and mounting method. Analogue types require an ExLine module, switching types an ExLine or ExBin-A module.

Model Type Measures Range Protection Zone
TFFR-2G TFFR-2G Analogue Temperature + humidity (room) Pt100 ±0.5 °C · 0–100% rH IP20 1, 2
TFR-2G TFR-2G Analogue Temperature (room) Pt100/Pt1000, –30…+60 °C IP30 1, 2
TFR-2G3D TFR-2G3D Analogue Temperature (room) Pt100/Pt1000, –30…+60 °C IP65 1, 2, 22
TFM-2G TFM-2G Analogue Average temperature (ventilation duct) Pt100, –20…+70 °C, capillary 0.4/3/6 m IP65 1, 2
TFR-AN-2G3D TFR-AN-2G3D Analogue Surface/contact temperature (pipe) Pt100, –30…+110 °C IP65 1, 2, 22
FFR-2G FFR-2G Analogue Humidity (room) 0–100% rH, 0…+50 °C IP20 1, 2
FFK-2G FFK-2G Analogue Humidity (duct) 0–100% rH, 0…+60 °C IP64 (probe IP40) 1, 2
TFK-2G3D TFK-2G3D Analogue Temperature (duct) Pt100/Pt1000, –30…+150 °C IP65 1, 2, 22
TFH-2G TFH-2G Analogue Temperature (cable/immersion) Pt100/Pt1000, –50…+250 °C depending on cable IP68 (-IP68 version) 1, 2
DBK-2G DBK-2G Switching Differential pressure 20–300 / 50–500 / 100–1,000 / 500–2,000 / 1,000–5,000 Pa IP54 1, 2
DBK-2G3D DBK-2G3D Switching Differential pressure 40–125 / 100–400 / 350–1,400 / 1,000–5,000 Pa IP65 1, 2, 22
TBT-2G TBT-2G / TBT-VA-2G Switching Temperature of liquids/gases (immersion) 0–60 / 0–90 / 0–120 / 50–140 °C IP65 / IP54 1, 2
TBT-...-U-2G TBT-...-U-2G / TBT-VA-2G-...-U Switching Temperature of liquids/gases (immersion, internal adjustment; also TBT-FF-2G with remote sensor) 0–90 / 0–120 °C (VA also –35…+35 °C) IP65 (brass) / IP54 (VA) / IP20 (FF) 1, 2
TBK-FR-2G TBK-FR-2G Switching Frost protection –10…+15 °C, capillary 1.8/3/6 m IP65 1, 2
TBK-2G TBK-2G Switching Thermostat (duct) 0–60 / 0–90 / 50–140 °C IP20 1, 2
TBR-2G TBR-2G Switching Thermostat (room) 0–40 / 0–60 °C IP54 1, 2
TBR-2G3D TBR-2G3D Switching Thermostat (room) –35…+30 / 0…+60 °C IP65 1, 2, 22
TBR-2-2G TBR-2-2G Switching Thermostat (room, 2-stage) 0–40 °C IP54 1, 2
FBR-2G FBR-2G Switching Hygrostat (room) 35–100% rH IP20 1, 2
FBK-2G FBK-2G Switching Hygrostat (duct) 35–95% rH IP44 1, 2
WFBK-2G WFBK-2G Switching Air flow switch (vane, duct) Switches from approx. 1 m/s air velocity IP65 1, 2
SWBT-2G SWBT-2G Switching Liquid flow switch (pipe) Max. 11 bar, brass / stainless steel (-VA) IP65 1, 2
LGW-2G-SIL LGW-2G-…-SIL Switching Differential pressure (SIL) 40–300 / 100–1,000 / 250–5,000 / 3,000–15,000 Pa IP54 1, 2

Click a row to open the product datasheet.

Designation overview

What the model designation means

TF... / FF...

Analogue (resistance) temperature probe (TF) or humidity probe (FF) – requires an ExLine module.

TB... / FB...

Switching thermostat (TB) or hygrostat (FB) with potential-free contact – ExLine module or ExBin-A.

DBK / LGW / WFBK / SWBT

Switching pressure and flow probes (differential pressure, air/liquid flow).

2G / 2G3D

Certification class: 2G = Zones 1/2 (gases), 2G3D = also Zone 22 (dust).

-U

Setting knob inside the housing instead of outside – protection against accidental/unauthorised changes to the setting.

-FF

Remote (capillary) sensor – version with a remote sensor instead of a direct immersion sensor.

-VA

Version with a stainless steel thermowell (1.4571), e.g. TBT-VA-2G.

Simple apparatus

EN 60079-11, cl. 5.7

ExSens probes are classified as “simple apparatus” – they have no Ex marking of their own; intrinsic safety is ensured via the connected ExLine/ExBin-A module.

Production quality – BVS ATEX ZQS/E136

DEKRA, valid until 2028

The manufacturer has a certified production quality system (DEKRA).

Datasheets – individual probes

Certificates