EN
Home Products ExBin / RedBin / InBin
ATEX certification IECEx Zone 1 · 2 · 21 · 22

ExBin / RedBin / InBin.

Binary (switching) transmitter in three versions: ExBin for Zones 1, 2, 21, 22, RedBin for the less stringent Zones 2 and 22, InBin for standard non-hazardous areas. Potential-free contact for pressure, frost protection and temperature/humidity.

0–5,000 Papressure range (ExBin-P)
–10…+15 °Cfrost protection (ExBin-FR)
IP66protection rating
24 VAC/DC power supply
–20…+50 °Coperating temperature
ExBin-P – binary pressure sensor for potentially explosive atmospheres ATEX certification

Key features

  • ExBin-P: pressure switch with digitally adjustable switching point, 1 or 2 contacts
  • ExBin-FR: frost protection thermostat with 3 m or 6 m capillary, range –10…+15 °C
  • ExBin-A: switching (isolating) module for 1–2 passive intrinsically safe sensors (thermostats, hygrostats, pressure switches)
  • ExBin-D: transmitter for the external ExPro-B probe (temperature and/or humidity, switching output)
  • Power supply 24 V AC/DC ±20%
  • Aluminium housing IP66, optional all-stainless-steel version
  • Also available as RedBin (Zone 2/22) and InBin (safe area)

Applications

Filter monitoring Frost protection of heat exchangers Thermostatic control Fan monitoring
ExBin-D requires a separate ExPro-B probe (temperature/humidity) – only 1 probe can be connected to one transmitter. ExBin-A evaluates max. 2 external switching sensors.

Technical data

Mechanical

Dimensions – aluminium
~180 × 107 × 68 mm (ExBin-A ~177 mm)
Dimensions – stainless steel
~195 × 127 × 70 mm
Weight
~950 g (aluminium) / ~2.5 kg (stainless steel)
Housing
Aluminium IP66 / optionally stainless steel (P/A/D only, ExBin-FR has no stainless steel variant)

Measurement and switching

ExBin-P ranges
0–100 / 0–500 / 0–5,000 Pa (adjustable from 5/25/250 Pa)
ExBin-P accuracy
Piezo pressure sensor, max. ±5% of range ±1 Pa
ExBin-FR range
–10…+15 °C, capillary 3 m (FR3) / 6 m (FR6)
ExBin-FR accuracy
Hysteresis ~6 K, accuracy ±3 K
ExBin-D + ExPro-B
–40…+125 °C (50 mm probe: –40…+80 °C) · 0–100% rH
Output
1–2 potential-free contacts (ExBin-P-2 and ExBin-D-2: 2 contacts)
Contact switching capacity
max. 0.5 A / 30 V AC/DC · 0.1 A / 250 VAC · 0.1 A / 220 VDC

Electrical

Power supply
24 V AC/DC ±20%
Power consumption
~4 W (150 mA)
Galvanic isolation
min. 1.5 kV
Cable glands
2× M16×1.5 (standard/-CT) · M20×1.5 (-VA/-OCT/-OVA)

Environment and certification

Protection rating
IP66
Operating temperature
–20…+50 °C
Humidity
0–95% rH, non-condensing
ATEX category
II 2(1)G / II 2(1)D
ATEX marking
Ex eb mb [ia Ga] IIC T6…T4 Gb / Ex tb [ia Da] IIIC T80…T130 °C Db

ExBin offers four functional variants according to the measured/switched variable. All are also available as RedBin (Zone 2/22) and InBin (safe area).

Variant Function Range Output
ExBin-P Pressure switch 0–100 / 0–500 / 0–5,000 Pa 1–2 contacts
ExBin-FR3 / FR6 Frost protection thermostat –10…+15 °C, capillary 3/6 m 1 contact
ExBin-A1 / A2 Switching module for passive Ex-i sensors 1 channel (A1) or 2 channels (A2) Relay contact
ExBin-D / D-2 Transmitter for the ExPro-B probe –40…+125 °C · 0–100% rH 1 contact (D) / 2 contacts (D-2)

Designation overview

What the designations and zone variants mean

ExBin-P

Binary (switching) pressure sensor – unlike ExCos-P, it has no modulating output, only a contact.

ExBin-FR

Frost protection of heat exchangers, capillary sensor along the fins.

ExBin-A

Switching (isolating) module – allows passive intrinsically safe sensors (TBR, FBR, DBK…) to be connected without the need for a separate Ex-i barrier in the control cabinet.

ExBin-D

Requires an ExPro-B probe (sold separately, max. 1 per transmitter).

RedBin

The same transmitter for Zone 2/22, less stringent category (II 3(1) G/D).

InBin

Version for standard environments (NOT intended for potentially explosive atmospheres), paired with InPro-B.

Installation and mounting accessories for ExBin-P/FR/A/D sensors and the ExPro-B probe.

Mounting and installation accessories

Details and datasheets – see the Accessories page

Small mounting accessories without a separate datasheet of their own. A complete overview including available datasheets is on the central Accessories page.

CodeFunction
Installation-Kit-2Installation kit for ExBin-P – 2 m pressure tube (Ø 6 mm) + 2 plastic nipples
Installation-Kit-1.3 / -1.6Installation kit for the ExBin-FR3 / ExBin-FR6 frost protection thermostat (capillary 3 m / 6 m)
MKR-VA/ALMounting bracket for installation on circular ducts up to Ø 600 mm
WS-CBRStainless steel weather protection cover for outdoor installations
Kit-S8-CBR2× cable gland M16×1.5 mm, Ex-e, nickel-plated brass
Kit-Offs-GL-CBR2× cable gland M20×1.5 mm, Ex-d, for armoured cables
Kit-PTC-CBR2× connection pipe for Ø 6 mm fittings, stainless steel 316L
VL3ExPro-B probe extension cable, 3 m – for ExBin-D/RedBin-D
MFK / TH-VA / Kit-FA-VAMounting flange, stainless steel thermowell and filter cap for the ExPro-B probe – see the probes page

Details and datasheets: Accessories

ATEX – Ex eb mb [ia Ga] IIC T6…T4 Gb

EPS14ATEX1657X

European certification for explosive gas atmospheres. Category 2(1)G – Zones 1 and 2, group IIC.

Zone 1 Zone 2

ATEX – Ex tb [ia Da] IIIC T80…T130 °C Db

EPS14ATEX1657X

Certification for dust atmospheres. Temperature class depends on the housing material and ambient temperature.

Zone 21 Zone 22

IECEx

IECEx EPS 14.0074X

International IECEx certification for use outside the EU. Covers both gas and dust zones.

RedBin – separate certification

EPS14ATEX1658X · IECEx EPS 14.0075X

The Zone 2/22 version has its own certificates with a less stringent category (II 3(1) G/D).

Catalogue

Datasheets – ExBin (Zone 1/2/21/22)

Datasheets – RedBin (Zone 2/22)

Datasheets – InBin (non-hazardous areas)

Certificates

Declarations of conformity