Pressure, temperature and humidity transmitter in three versions: ExCos for Zones 1, 2, 21, 22, RedCos for the less stringent Zones 2 and 22, InCos for standard non-hazardous areas. Modulating analogue output for direct integration into a BMS.
Key features
Applications
Technical data
Mechanical
Measurement and signal
Electrical
Environment and certification
ExCos-P measures pressure/differential pressure directly; ExCos-D is a universal transmitter for the external ExPro-C probe (temperature, humidity or combined). Both series are also available as RedCos (Zone 2/22) and InCos (safe area).
7 models by range, analogue output 0–10 V / (0)4–20 mA
| Model | Range | Adjustable from | Max. overpressure |
|---|---|---|---|
| ExCos-P-100 | ±100 Pa | 20 Pa | 25,000 Pa |
| ExCos-P-250 | ±250 Pa | 50 Pa | 25,000 Pa |
| ExCos-P-500 | ±500 Pa | 100 Pa | 50,000 Pa |
| ExCos-P-1250 | ±1,250 Pa | 250 Pa | 50,000 Pa |
| ExCos-P-2500 | ±2,500 Pa | 500 Pa | 50,000 Pa |
| ExCos-P-5000 | ±5,000 Pa | 1,000 Pa | 75,000 Pa |
| ExCos-P-7500 | ±7,500 Pa | 1,500 Pa | 120,000 Pa |
Requires an ExPro-C probe – see the separate ExPro page
| Model | Measures | Range (with ExPro-C probe) | Probe |
|---|---|---|---|
| ExCos-D | Temperature and/or humidity | –40…+125 °C (probes from 50 mm: –40…+80 °C) · 0–100% rH | ExPro-CT/CF/CTF |
What the designations and zone variants mean
The number in the designation = full pressure range in Pa (e.g. “P-2500” = ±2,500 Pa).
Universal transmitter without its own sensor – requires an ExPro-C probe (sold separately).
The same transmitter for Zone 2/22 (less stringent certification than ExCos for Zone 1/2/21/22).
Version for standard environments (NOT intended for potentially explosive atmospheres), paired with InPro-C.
Installation and mounting accessories for ExCos-P / ExCos-D sensors and the ExPro-C probe.
Details and datasheets – see the Accessories page
Small mounting accessories without a separate datasheet of their own. A complete overview including available datasheets is on the central Accessories page.
| Code | Function |
|---|---|
| Installation-Kit-2 | Installation kit for ExCos-P – 2 m pressure tube (Ø 6 mm) + 2 plastic nipples |
| MKR-VA/AL | Mounting bracket for installation on circular ducts up to Ø 600 mm |
| WS-CBR | Stainless steel weather protection cover for outdoor installations |
| VL3 | ExPro-C probe extension cable, 3 m – for ExCos-D/RedCos-D |
| MFK / TH-VA / Kit-FA-VA | Mounting flange, stainless steel thermowell and filter cap for the ExPro-C probe – see the probes page |
Details and datasheets: Accessories
European certification for explosive gas atmospheres. Category 2(1)G – Zones 1 and 2, group IIC.
Certification for dust atmospheres. The temperature class depends on the housing material and ambient temperature: aluminium version T80 °C, stainless steel T95–T130 °C.
International IECEx certification for use outside the EU. Covers both gas and dust zones.
The Zone 2/22 version has its own certificates with a less stringent category (II 3(1) G/D).
Catalogue and datasheets
Datasheets – P (pressure)
Datasheets – D (temperature/humidity)
Certificates
Declarations of conformity